 "revision": "S02",
 "date": "2026-09-12",
 "supply": "BESCOM three-phase, 10 kW sanctioned (LT commercial); premises on its own sub-meter",
 "rooms": [
  {
   "id": "GF-01",
   "floor": "GF",
   "name": "Four-person cabin",
   "sqft": 234,
   "seats": 4,
   "lux": 300,
   "fans": 0,
   "sockets6": 5,
   "sockets16": 2,
   "notes": "AC on its own 20 A MCB; 2 duplex desk boards; 1 general 16 A.",
   "extra": [],
   "lights": 5,
   "lights_w": 180,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 0,
   "exhaust": 0,
   "seats_w": 380,
   "ac_units": [
    "0.8-ton inverter split"
   ],
   "ac_w": 800,
   "ac_run_w": 500,
   "extra_w": 0,
   "connected_w": 1360,
   "typical_w": 874
  },
  {
   "id": "GF-02",
   "floor": "GF",
   "name": "Reception and goodies store",
   "sqft": 90,
   "seats": 3,
   "lux": 200,
   "fans": 1,
   "sockets6": 5,
   "sockets16": 1,
   "notes": "Standing check-in; printer on the 16 A point.",
   "extra": [
    {
     "item": "Display + label printer",
     "connected_w": 90,
     "average_w": 40,
     "feed": "raw",
     "point": "16A"
    }
   ],
   "lights": 4,
   "lights_w": 48,
   "lamp": "LED downlight 12 W",
   "fans_w": 35,
   "exhaust": 0,
   "seats_w": 285,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 90,
   "connected_w": 458,
   "typical_w": 303
  },
  {
   "id": "GF-03",
   "floor": "GF",
   "name": "Rear sanitary space",
   "sqft": 68,
   "seats": 0,
   "lux": 100,
   "fans": 0,
   "exhaust": 1,
   "sockets6": 1,
   "sockets16": 0,
   "notes": "No geyser proposed (each would add 2-3 kW).",
   "extra": [],
   "lights": 2,
   "lights_w": 24,
   "lamp": "LED downlight 12 W",
   "fans_w": 0,
   "seats_w": 0,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 49,
   "typical_w": 39
  },
  {
   "id": "GF-04",
   "floor": "GF",
   "name": "Kitchen",
   "sqft": 189,
   "seats": 0,
   "lux": 200,
   "fans": 1,
   "exhaust": 1,
   "sockets6": 2,
   "sockets16": 4,
   "notes": "Four dedicated 16 A points; kettle and microwave on separate MCBs; house rule: not both during an event peak.",
   "extra": [
    {
     "item": "Refrigerator",
     "connected_w": 300,
     "average_w": 150,
     "feed": "raw",
     "point": "16A"
    },
    {
     "item": "Kettle",
     "connected_w": 1500,
     "average_w": 0,
     "feed": "raw",
     "point": "16A"
    },
    {
     "item": "Microwave",
     "connected_w": 1200,
     "average_w": 0,
     "feed": "raw",
     "point": "16A"
    },
    {
     "item": "Water purifier / dispenser (no heating)",
     "connected_w": 40,
     "average_w": 40,
     "feed": "raw",
     "point": "16A"
    }
   ],
   "lights": 4,
   "lights_w": 80,
   "lamp": "LED batten 20 W (IP65 outdoors)",
   "fans_w": 35,
   "seats_w": 0,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 3040,
   "connected_w": 3180,
   "typical_w": 298
  },
  {
   "id": "GF-06",
   "floor": "GF",
   "name": "Stair-side sanitary space",
   "sqft": 33,
   "seats": 0,
   "lux": 100,
   "fans": 0,
   "exhaust": 1,
   "sockets6": 1,
   "sockets16": 0,
   "notes": "",
   "extra": [],
   "lights": 1,
   "lights_w": 12,
   "lamp": "LED downlight 12 W",
   "fans_w": 0,
   "seats_w": 0,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 37,
   "typical_w": 32
  },
  {
   "id": "GF-07",
   "floor": "GF",
   "name": "Enclosed booth",
   "sqft": 45,
   "seats": 2,
   "lux": 300,
   "fans": 0,
   "sockets6": 2,
   "sockets16": 0,
   "notes": "Glass-fronted; shares GF-10 air; small oscillating fan point if needed.",
   "extra": [],
   "lights": 3,
   "lights_w": 36,
   "lamp": "LED downlight 12 W",
   "fans_w": 0,
   "exhaust": 0,
   "seats_w": 130,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 166,
   "typical_w": 113
  },
  {
   "id": "GF-08",
   "floor": "GF",
   "name": "Balcony cafe",
   "sqft": 204,
   "seats": 6,
   "lux": 100,
   "fans": 2,
   "sockets6": 4,
   "sockets16": 1,
   "outdoor": true,
   "notes": "IP44 sockets and IP65 fittings; on an RCBO of its own.",
   "extra": [],
   "lights": 3,
   "lights_w": 60,
   "lamp": "LED batten 20 W (IP65 outdoors)",
   "fans_w": 70,
   "exhaust": 0,
   "seats_w": 390,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 520,
   "typical_w": 379
  },
  {
   "id": "GF-09",
   "floor": "GF",
   "name": "Lounge and presentation hall",
   "sqft": 300,
   "seats": 24,
   "lux": 250,
   "fans": 2,
   "sockets6": 13,
   "sockets16": 3,
   "dimmable": true,
   "notes": "24 audience seats assumed for events (4 lounge chairs day-to-day). Two AC points on 20 A MCBs; AV rack fed from the UPS; 3 audience duplex boards along the walls; projector point at the ceiling opposite the screen wall; PTZ camera facing the screen; mic receiver at the rack.",
   "extra": [
    {
     "item": "Projector (ceiling)",
     "connected_w": 350,
     "average_w": 300,
     "feed": "ups",
     "point": "6A"
    },
    {
     "item": "Streaming / recording PC + capture",
     "connected_w": 250,
     "average_w": 200,
     "feed": "ups",
     "point": "6A"
    },
    {
     "item": "Active speakers x2",
     "connected_w": 120,
     "average_w": 60,
     "feed": "ups",
     "point": "6A"
    },
    {
     "item": "Wireless mic receiver + audio interface",
     "connected_w": 35,
     "average_w": 30,
     "feed": "ups",
     "point": "6A"
    },
    {
     "item": "PTZ recording camera (PoE)",
     "connected_w": 20,
     "average_w": 20,
     "feed": "ups",
     "point": "PoE"
    }
   ],
   "lights": 5,
   "lights_w": 180,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 70,
   "exhaust": 0,
   "seats_w": 1560,
   "ac_units": [
    "1.5-ton inverter split",
    "1.5-ton inverter split"
   ],
   "ac_w": 3000,
   "ac_run_w": 2400,
   "extra_w": 775,
   "connected_w": 5585,
   "typical_w": 4280
  },
  {
   "id": "GF-10",
   "floor": "GF",
   "name": "Coworking commons",
   "sqft": 386,
   "seats": 38,
   "lux": 300,
   "fans": 5,
   "sockets6": 19,
   "sockets16": 2,
   "notes": "Three table-mounted power rails (5 duplex each) plus a 4-duplex strip under the window counter; two 16 A general points.",
   "extra": [],
   "lights": 7,
   "lights_w": 252,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 175,
   "exhaust": 0,
   "seats_w": 2470,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 2897,
   "typical_w": 1561
  },
  {
   "id": "FF-01",
   "floor": "FF",
   "name": "Rear support / sanitary",
   "sqft": 85,
   "seats": 0,
   "lux": 100,
   "fans": 0,
   "exhaust": 1,
   "sockets6": 1,
   "sockets16": 0,
   "notes": "",
   "extra": [],
   "lights": 2,
   "lights_w": 24,
   "lamp": "LED downlight 12 W",
   "fans_w": 0,
   "seats_w": 0,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 49,
   "typical_w": 39
  },
  {
   "id": "FF-02",
   "floor": "FF",
   "name": "Workshop terrace (lab room once enclosed)",
   "sqft": 260,
   "seats": 4,
   "lux": 500,
   "fans": 2,
   "exhaust": 1,
   "sockets6": 10,
   "sockets16": 9,
   "notes": "Enclosure is a prerequisite for printers and GPUs (dust, humidity, rain). UPS output DB here: 2 x 16 A GPU, 3 x 16 A printers, 2 x 6 A rack. Raw: bench 6 x 6 A + 2 x 16 A, soldering/extraction 16 A, general 16 A. 500 lux task lighting.",
   "extra": [
    {
     "item": "GPU workstation x2",
     "connected_w": 1400,
     "average_w": 1000,
     "feed": "ups",
     "point": "16A"
    },
    {
     "item": "3D printers x3 (P1S, A1, one spare bay)",
     "connected_w": 850,
     "average_w": 300,
     "feed": "ups",
     "point": "16A"
    },
    {
     "item": "Network rack: router, PoE switch (10 cams + PTZ), NVR, NAS",
     "connected_w": 220,
     "average_w": 200,
     "feed": "ups",
     "point": "6A"
    },
    {
     "item": "Access controller + 6 door locks/readers (12 V via rack)",
     "connected_w": 108,
     "average_w": 108,
     "feed": "ups",
     "point": "PoE"
    },
    {
     "item": "Soldering station + fume extraction",
     "connected_w": 180,
     "average_w": 80,
     "feed": "raw",
     "point": "16A"
    },
    {
     "item": "Bench instruments (scope, PSU, meter)",
     "connected_w": 150,
     "average_w": 60,
     "feed": "raw",
     "point": "6A"
    }
   ],
   "lights": 8,
   "lights_w": 288,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 70,
   "seats_w": 380,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 2908,
   "connected_w": 3671,
   "typical_w": 2282
  },
  {
   "id": "FF-03",
   "floor": "FF",
   "name": "Two- and four-person cabins",
   "sqft": 228,
   "seats": 6,
   "lux": 300,
   "fans": 0,
   "sockets6": 7,
   "sockets16": 4,
   "notes": "Two cabins: 2-seat (2 duplex) and 4-seat (4 duplex, sliding entrance); one AC and one 16 A general point each.",
   "extra": [],
   "lights": 5,
   "lights_w": 180,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 0,
   "exhaust": 0,
   "seats_w": 570,
   "ac_units": [
    "0.8-ton inverter split",
    "0.8-ton inverter split"
   ],
   "ac_w": 1600,
   "ac_run_w": 1000,
   "extra_w": 0,
   "connected_w": 2350,
   "typical_w": 1507
  },
  {
   "id": "FF-04",
   "floor": "FF",
   "name": "Stair landing and gallery (twin cabins)",
   "sqft": 410,
   "seats": 8,
   "lux": 300,
   "fans": 1,
   "sockets6": 10,
   "sockets16": 4,
   "notes": "Two four-table cabins: 4 duplex + AC + 16 A each; landing gets 2 duplex and a fan.",
   "extra": [],
   "lights": 8,
   "lights_w": 288,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 35,
   "exhaust": 0,
   "seats_w": 760,
   "ac_units": [
    "0.8-ton inverter split",
    "0.8-ton inverter split"
   ],
   "ac_w": 1600,
   "ac_run_w": 1000,
   "extra_w": 0,
   "connected_w": 2683,
   "typical_w": 1740
  },
  {
   "id": "FF-05",
   "floor": "FF",
   "name": "Bathroom",
   "sqft": 40,
   "seats": 0,
   "lux": 100,
   "fans": 0,
   "exhaust": 1,
   "sockets6": 1,
   "sockets16": 0,
   "notes": "No geyser proposed.",
   "extra": [],
   "lights": 1,
   "lights_w": 12,
   "lamp": "LED downlight 12 W",
   "fans_w": 0,
   "seats_w": 0,
   "ac_units": [],
   "ac_w": 0,
   "ac_run_w": 0,
   "extra_w": 0,
   "connected_w": 37,
   "typical_w": 32
  },
  {
   "id": "FF-06",
   "floor": "FF",
   "name": "Office twin cabins",
   "sqft": 348,
   "seats": 8,
   "lux": 300,
   "fans": 0,
   "sockets6": 10,
   "sockets16": 4,
   "notes": "Two four-table cabins: 4 duplex + AC + 16 A each; 2 IP44 duplex on the balcony. These are the largest cabins: if the glazing is unshaded, specify 1-ton units here (about +0.15 kW each running).",
   "extra": [],
   "lights": 7,
   "lights_w": 252,
   "lamp": "2x2 LED panel 36 W",
   "fans_w": 0,
   "exhaust": 0,
   "seats_w": 760,
   "ac_units": [
    "0.8-ton inverter split",
    "0.8-ton inverter split"
   ],
   "ac_w": 1600,
   "ac_run_w": 1000,
   "extra_w": 0,
   "connected_w": 2612,
   "typical_w": 1683
  }
 ],
 "cameras": [
  {
   "id": "C1",
   "floor": "GF",
   "room": "GF-02",
   "view": "Main entrance (side C door) from inside reception"
  },
  {
   "id": "C2",
   "floor": "GF",
   "room": "GF-02",
   "view": "Reception desk and commons door"
  },
  {
   "id": "C3",
   "floor": "GF",
   "room": "GF-10",
   "view": "Commons, from the curved front wall toward the tables"
  },
  {
   "id": "C4",
   "floor": "GF",
   "room": "GF-09",
   "view": "Hall wide view including stair foot (separate from the PTZ recording camera)"
  },
  {
   "id": "C5",
   "floor": "GF",
   "room": "GF-04",
   "view": "Kitchen doorway and GF-09 passage"
  },
  {
   "id": "C6",
   "floor": "GF",
   "room": "GF-08",
   "view": "Balcony cafe (IP66 dome)"
  },
  {
   "id": "C7",
   "floor": "FF",
   "room": "FF-04",
   "view": "First-floor landing and gallery void"
  },
  {
   "id": "C8",
   "floor": "FF",
   "room": "FF-02",
   "view": "Workshop: printers, bench and GPU rack"
  },
  {
   "id": "C9",
   "floor": "GF",
   "room": "GF-04",
   "view": "Kitchen / rear service door A3 (added so every access door is covered)"
  },
  {
   "id": "C10",
   "floor": "FF",
   "room": "FF-06",
   "view": "Lower-cabin balcony door A6 and the FF-06 corridor"
  }
 ],
 "access_doors": [
  {
   "id": "A1",
   "floor": "GF",
   "room": "GF-02",
   "where": "Main entrance, side C (4 ft door)",
   "watts": 18
  },
  {
   "id": "A2",
   "floor": "GF",
   "room": "GF-10",
   "where": "Commons street-side door (position to confirm on site)",
   "watts": 18
  },
  {
   "id": "A3",
   "floor": "GF",
   "room": "GF-04",
   "where": "Kitchen / rear service door (position to confirm on site)",
   "watts": 18
  },
  {
   "id": "A4",
   "floor": "FF",
   "room": "FF-04",
   "where": "Stair-head door to the first floor",
   "watts": 18
  },
  {
   "id": "A5",
   "floor": "FF",
   "room": "FF-02",
   "where": "Workshop terrace door",
   "watts": 18
  },
  {
   "id": "A6",
   "floor": "FF",
   "room": "FF-06",
   "where": "Lower-cabin balcony door",
   "watts": 18
  }
 ],
 "scenarios": {
  "design_25": {
   "items": [
    [
     "Cabin ACs, 4 of 7 running at 25 C, 85% simultaneity",
     1700
    ],
    [
     "Cabin desks, 14 seats at 70%",
     931
    ],
    [
     "Commons, 11 seats with laptops",
     715
    ],
    [
     "Reception, booth, cafe (partial)",
     370
    ],
    [
     "Lighting, 50% of installed (daylight)",
     958
    ],
    [
     "Fans and exhausts, 80%",
     512
    ],
    [
     "Workshop: GPUs, printers, rack, bench (average)",
     1748
    ],
    [
     "Kitchen average (fridge, purifier)",
     190
    ],
    [
     "Battery chargers at float",
     300
    ]
   ],
   "total_kw": 7.42
  },
  "full_house": {
   "items": [
    [
     "Cabin ACs, 7 x 0.8 t inverter at 25 C, 85% simultaneity",
     2975
    ],
    [
     "Cabin desks, 26 seats at 70%",
     1729
    ],
    [
     "Commons, 21 of 38 seats with laptops",
     1365
    ],
    [
     "Reception, booth, cafe (partial)",
     564
    ],
    [
     "Lighting, 50% of installed (daylight)",
     958
    ],
    [
     "Fans and exhausts, 80%",
     512
    ],
    [
     "Workshop: GPUs, printers, rack, bench (average)",
     1748
    ],
    [
     "Kitchen average (fridge, purifier; kettle/microwave excluded)",
     190
    ],
    [
     "Battery chargers at float (UPS + 2 inverters)",
     300
    ]
   ],
   "total_kw": 10.34
  },
  "event": {
   "items": [
    [
     "Hall ACs, 2 x 1.5 t inverter running",
     2400
    ],
    [
     "Hall AV (projector, PC, audio, camera) average",
     610
    ],
    [
     "Hall audience laptops, 12 of 24",
     780
    ],
    [
     "Two cabins still occupied (AC + desks); rule: cabin ACs off by the event start",
     1532
    ],
    [
     "Commons, 12 seats",
     780
    ],
    [
     "Lighting, 75% (evening)",
     1437
    ],
    [
     "Fans and exhausts, 70%",
     448
    ],
    [
     "Workshop average (GPU job running)",
     1748
    ],
    [
     "Kitchen average + one kettle cycle allowed",
     640
    ],
    [
     "Battery chargers at float",
     300
    ]
   ],
   "total_kw": 10.68
  },
  "forbidden_worst": {
   "items": [
    [
     "Cabin ACs, 7 x 0.8 t inverter at 25 C, 85% simultaneity",
     2975
    ],
    [
     "Cabin desks, 26 seats at 70%",
     1729
    ],
    [
     "Commons, 21 of 38 seats with laptops",
     1365
    ],
    [
     "Reception, booth, cafe (partial)",
     564
    ],
    [
     "Lighting, 50% of installed (daylight)",
     958
    ],
    [
     "Fans and exhausts, 80%",
     512
    ],
    [
     "Workshop: GPUs, printers, rack, bench (average)",
     1748
    ],
    [
     "Kitchen average (fridge, purifier; kettle/microwave excluded)",
     190
    ],
    [
     "Battery chargers at float (UPS + 2 inverters)",
     300
    ],
    [
     "Hall ACs + AV + audience (event on top of full house)",
     3790
    ],
    [
     "Kettle and microwave together",
     2700
    ],
    [
     "Bulk charging all three battery banks (max charger current)",
     1900
    ]
   ],
   "total_kw": 18.73
  },
  "connected_kw": 25.71
 },
 "phases": {
  "R": [
   [
    "GF-01 AC",
    425.0
   ],
   [
    "FF-04 a/b ACs",
    850.0
   ],
   [
    "GF lighting + fans",
    474.0
   ],
   [
    "Commons rails 1-2 (10 of 21 laptops)",
    650
   ],
   [
    "GF-01 + FF-04 desks",
    798.0
   ],
   [
    "Hall AC 1 (event only)",
    0
   ]
  ],
  "Y": [
   [
    "FF-03 a/b ACs",
    850.0
   ],
   [
    "Kitchen",
    190
   ],
   [
    "Reception, booth, cafe",
    620
   ],
   [
    "Commons rails 3 + counter (11 laptops)",
    715
   ],
   [
    "FF lighting + fans",
    510.0
   ],
   [
    "FF-03 desks",
    399.0
   ],
   [
    "GF inverter charger (float)",
    100
   ],
   [
    "Hall AC 2 (event only)",
    0
   ]
  ],
  "B": [
   [
    "FF-06 a/b ACs",
    850.0
   ],
   [
    "UPS input: workshop + rack + charger float",
    1848
   ],
   [
    "FF-06 desks",
    532.0
   ],
   [
    "FF inverter charger (float)",
    100
   ]
  ]
 },
 "phase_kw": {
  "R": 3.2,
  "Y": 3.38,
  "B": 3.33
 },
 "ups": {
  "rating_kva": 3.0,
  "rating_kw_at_pf0_9": 2.7,
  "connected_w": 3353,
  "average_w": 2218,
  "backup_h": 2.0,
  "energy_needed_kwh": 4.93,
  "lifepo4_kwh_at_80pct_dod": 6.16,
  "lifepo4_option": "48 V 120 Ah LiFePO4 (5.8 kWh) minimum; 48 V 150 Ah (7.2 kWh) recommended for headroom",
  "lead_acid_option": "4 x 12 V 200 Ah tubular at 48 V (9.6 kWh nominal, ~4.8 kWh usable at 50% DoD): meets 2 h only at average load, ~180 kg, needs a ventilated rack",
  "charger_limit_w": 500,
  "note": "Connected UPS load (3.25 kW) exceeds a 3 kVA unit; average (2.0 kW) fits. Rule: during an event the AV rides on the UPS while printer starts are held, or step up to 5 kVA."
 },
 "inverters": {
  "GF": {
   "rating": "2 kVA / 24 V pure sine",
   "battery": "2 x 12 V 150 Ah tubular (3.6 kWh nominal)",
   "covers": "GF lights, 8 BLDC fans, reception board, 2 commons duplex per rail",
   "backup_est_h": 1.7
  },
  "FF": {
   "rating": "1.5 kVA / 24 V pure sine",
   "battery": "2 x 12 V 150 Ah tubular (3.6 kWh nominal)",
   "covers": "FF lights, 3 BLDC fans, one duplex per cabin",
   "backup_est_h": 2.4
  }
 }
}